3.3.2 Control terminals
The control and software functionality can be freely configured for economical opera-
tion with a safe function.
Expansion module EM-IO-02
0.14 … 1.5 mm
AWG 30 … 16
2
Wieland DST85 / RM3,5
0.14 … 1.5 mm
AWG 30 … 16
2
0.25 … 1.0 mm
AWG 22 … 18
2
0.25 … 0.75 mm
AWG 22 … 20
2
0.2 … 0.3 Nm
1.8 … 2.7 lb-in
Caution!
T
he control inputs and outputs must be connected and disconnected free
of electrical power. Otherwise, components may be damaged.
The unit may only be connected with the power supply switched off.
Make sure that the frequency inverter is de-energized.
Socket X410A
Ter. Description
1
V
olta
g
e output 20 V, I
max
= 180 mA
1)
2 Earth / GND 20 V
3 Digital input EM-S1IND, U
max
= 30 V, 10 mA at 24 V, PLC compatible,
response time approx. 16 ms
4 Digital input EM-S2IND, U
max
= 30 V, 10 mA at 24 V, PLC compatible,
response time approx. 16 ms
5 Digital input EM-S3IND, U
max
= 30 V, 10 mA at 24 V, PLC compatible,
response time approx. 16 ms
6-7 Digital output EM-S1OUTD, make contact, U
max
= 24 V AC/DC, 1 A (ohmic)
Socket X410B
Ter. Description
1-2 Motor PTC connection EM-MPTC,
rated response resistance > 2.85 kOhm (PTC) according DIN 44081
3
A
nalo
g
input EM-S1INA, resolution 12 bit,
U
max
= ±10 V (Ri = 100 kΩ),
I
max
= ±20 mA (Ri = 250 Ω)
4
A
nalo
g
output EM-S1OUTA,
U
max
= ±10 V, I
max
= 2 mA, overload and short circuit proof
5 System bus, CAN low
6 System bus, CAN high
7 Earth / GND
1)
T
he power supply at terminal X210A.1 may be loaded with a maximum current o
f
I
max
= 180 mA. Relative to the application, the maximum current available will be
reduced by the further control outputs in the basic device and the expansion mod-
ule.